常用
压缩机类型
旋转
送风方式
水平
回风方式
后置返回
制冷充电
1.36 KG
风量
566.34 lps
涌流安培图
65A
冷凝泵容量
0.002 lps
输入
电源线数目
1
额定输入电压
200, 208, 220, 230
输入功率
2390 瓦数
输入频率
50 Hz +/- 3 Hz
设备安装有效高度
42U
输入端子类型
通讯与管理
控制面板
多功能液晶显示器状态管理控制台。
能量使用/效率
Load
|
Loss
|
25%
|
0.0%
|
50%
|
33.0%
|
75%
|
34.6%
|
100%
|
41.7%
|
ACSC101 | Loss: 33% | Load: 50% |
ACSC101 | Loss: 32.9% | Load: 51% |
ACSC101 | Loss: 32.9% | Load: 52% |
ACSC101 | Loss: 32.9% | Load: 53% |
ACSC101 | Loss: 32.9% | Load: 54% |
ACSC101 | Loss: 32.9% | Load: 55% |
ACSC101 | Loss: 32.9% | Load: 56% |
ACSC101 | Loss: 32.9% | Load: 57% |
ACSC101 | Loss: 32.9% | Load: 58% |
ACSC101 | Loss: 32.9% | Load: 59% |
ACSC101 | Loss: 33% | Load: 60% |
ACSC101 | Loss: 33% | Load: 61% |
ACSC101 | Loss: 33.1% | Load: 62% |
ACSC101 | Loss: 33.1% | Load: 63% |
ACSC101 | Loss: 33.2% | Load: 64% |
ACSC101 | Loss: 33.3% | Load: 65% |
ACSC101 | Loss: 33.4% | Load: 66% |
ACSC101 | Loss: 33.5% | Load: 67% |
ACSC101 | Loss: 33.6% | Load: 68% |
ACSC101 | Loss: 33.7% | Load: 69% |
ACSC101 | Loss: 33.8% | Load: 70% |
ACSC101 | Loss: 34% | Load: 71% |
ACSC101 | Loss: 34.1% | Load: 72% |
ACSC101 | Loss: 34.3% | Load: 73% |
ACSC101 | Loss: 34.4% | Load: 74% |
ACSC101 | Loss: 34.6% | Load: 75% |
ACSC101 | Loss: 34.8% | Load: 76% |
ACSC101 | Loss: 35% | Load: 77% |
ACSC101 | Loss: 35.2% | Load: 78% |
ACSC101 | Loss: 35.4% | Load: 79% |
ACSC101 | Loss: 35.6% | Load: 80% |
ACSC101 | Loss: 35.8% | Load: 81% |
ACSC101 | Loss: 36% | Load: 82% |
ACSC101 | Loss: 36.3% | Load: 83% |
ACSC101 | Loss: 36.5% | Load: 84% |
ACSC101 | Loss: 36.8% | Load: 85% |
ACSC101 | Loss: 37.1% | Load: 86% |
ACSC101 | Loss: 37.3% | Load: 87% |
ACSC101 | Loss: 37.6% | Load: 88% |
ACSC101 | Loss: 37.9% | Load: 89% |
ACSC101 | Loss: 38.2% | Load: 90% |
ACSC101 | Loss: 38.5% | Load: 91% |
ACSC101 | Loss: 38.8% | Load: 92% |
ACSC101 | Loss: 39.2% | Load: 93% |
ACSC101 | Loss: 39.5% | Load: 94% |
ACSC101 | Loss: 39.9% | Load: 95% |
ACSC101 | Loss: 40.2% | Load: 96% |
ACSC101 | Loss: 40.6% | Load: 97% |
ACSC101 | Loss: 40.9% | Load: 98% |
ACSC101 | Loss: 41.3% | Load: 99% |
ACSC101 | Loss: 41.7% | Load: 100% |
浏览上面的“能源利用率”图表线来查看的效率与负载比详情
此曲线可拟合测得的数据损失(包括冷凝器功耗)。损失以全部额定容量的百分比表示。所有测量工作均使用额定电力输入在“仅制冷”工作模式下进行。供气温度设定点:18 °C。回风温度:29 °C 干球;18 °C 湿球。冷凝器周围的空气温度:27 °C。不建议在额定容量的 50% 以下操作。
物理指标
高
1991.00 mm
宽
300.00 mm
深
1069.00 mm
净重
165.92 KG
运输重量
273.18 KG
运输高度
2156.00 mm
运输宽度
762.00 mm
运输长度
1138.00 mm
颜色
黑色
环境
存储温度
0 - 40 °C
存储相对湿度
0 - 95%
存储高度
0-4500米
听觉噪音距设备表面 1 m 处
80.00 dBA
相符性
管理机构认证
BSMI, C-tick, CE, EN 55022 A 级, FCC 15 部分 A 级, GOST, ICES-003, 列出的 UL, VDE, VCCI
标准质保
1 年(仅限零件), 厂家授权的启动装置提供 1 年现场保修或保换
可持续提供状态
RoHS
符合
REACH
REACH SVHC
PEP
Available in Documentation tab
EOLI
Available in Documentation tab
电池指令
符合
电池注意事项
其它的环境合规性
中国RoHS